FDTD解析によるウインドファーム共通接地に用いる連接接地線に関する一検討
◎村瀬 峻・長岡直人・馬場吉弘・雨谷昭弘(同志社大学)
For bare conductor or even in the case of insulated conductor, the difference in the lightning surge voltage is about 5%. Insulated conductor is effective for grounding wire considering the corrosion of the grounding wire. It is not limited to the connecting cable is necessarily lower the voltage, there is a case where there is no more grounding wire is low in steady-state voltage and maximum voltage in the tower at a distance from the lightning protection tower.